XMT-8 series digital temperature controller

Model number and parameters
Model numberExternal dimensionsPerforation dimensionsOnline store: 
XMTG-848x48x110 mm44 10x44 10 mmUS $39.99 - 101.6/ pieceOrder (40)
XMTE-848X96X110 mm44 10x92 10 mmUS $39.99 - 101.6/ pieceOrder (40)
XMTF-896x48x110 mm92 10x44 10 mmUS $39.99 - 101.6/ pieceOrder (40)
XMTD-872x72x110 mm68 10x68 10 mmUS $39.99 - 101.6/ pieceOrder (40)
XMTA-896x96x110 mm92 10x92 10 mmUS $39.99 - 101.6/ pieceOrder (40)
XMT-8160x80x110 mm152 10x76 10 mmUS $39.99 - 101.6/ pieceOrder (40)
XMT-8SPC software and single chip micocomputerFor RS485 type controllerUS $45.91/ pieceOrderAdd to Cart
General
Model number XMT-8 series
Accuracy ±0.5%F.S±1℃
Supply voltage 85-242Vac,50/60 Hz
Input type Thermocouple: K, J, S, B, E, N, T, WRe
RTD: Pt100, Cu50
Voltage: 0-5V, 1-5V, 0-1V, 0-100mV, 0-20mV (Need to be customized, default don't have)
Current: 0-20mA, 4-20mA, 0-10mA (Need to be customized, default don't have)
Output type Electromagnetic relay, SSR, current, triac (not in one product, need to be selected)
Auxiliary function Ramp/soak, communication (RS485 or RS232 interface)
Power consumption Less than 4W
Control method PID, or ON/OFF
Setting method Touch switch
Indication method 8-segment 4-digital display and LED indication
Alarms 1. Alarm quantity: XMTG-P: 1pcs, others: default is 1pcs, if 2pcs, need to be customized
2. Alarm form: ALM1: High limit alarm
ALM2: Low limit alarm
Hy-1: Positive deviation alarm
Hy-2: Negative deviation alarm
Sampling period 0.5s
Control period Electromagnetic relay output: 2-120s (can adjust), others: 2s
Operating temperature 0 to 50 ℃ (32 to 122 ℉)
Operating humidity 85% RH max, non-condensing
Alias name XMT-P series pid temperature controller, intelligent temperature controller
Output type and description
Electromagnetic relay Contact rating: 5A at 220Vac
Solid state relay Contact rating can be selected, order separately (Single phase 40AThree phase 40A)
Current Can be any value in 0-22mA
SCR Zero crossing pulse, Amplitude>3V, width>50us, the instrument's supply voltage and load must be same phase current
Auxiliary function
Ramp/soak 30 segments program, can set up or down ramp
Communication RS485 or RS232 interface (Standard Modbus RTU protocol, you need write the software yourself or buy the PC software from us)
Input type and measuring range
K -50-1300 ℃ (BoltPress springRingM12 probeM8 probeFlexible probeArmor high temperature resistantCustomized thread probe)
S -50-1700 ℃ (ProbeArmor)
B 0-1800 ℃
E 0-800 ℃ (BoltPress springRingProbeCustomized thread probe)
N 0-1300 ℃
T -200-350 ℃
WRe 0-2300 ℃
Pt100 -199.9-649.0 ℃ (BoltPress springRingProbePolish rodPolish rod waterproofPolish rod waterproof anticorrosiveFlexible probeCustomized thread probe)
Cu50 -50-150 ℃ (ProbePolish rod waterproof)
Voltage 0-5V, 1-5V 0.0-100.0 ℃