XMT-7 series digital temperature controller

Model number and parameters
Model numberSame modelExternal dimensionsPerforation dimensionsOnline store: 
XMTG-7XMTG-948x48x78 mm44 10x44 10 mmUS $13.79 - 17.28/ pieceOrder (19)
XMTE-7XMTE-948x96x72 mm44 10x92 10 mmUS $13.79 - 18.45/ pieceOrder (11)
XMTD-7XMTD-972x72x80 mm68 10x68 10 mmUS $13.79 - 17.28/ pieceOrder (10)
XMTD272x72x80 mm68 10x68 10 mm
XMTA-7XMTA-996x96x66 mm92 10x92 10 mmUS $13.79 - 17.28/ pieceOrder (10)
XMT-7XMT-9160x80x85 mm152 10x76 10 mmUS $16.12 - 19.61/ pieceOrder (10)
General
Model number XMT-7 series
Accuracy RTD input: ±0.5%FS±1℃, Others input: ±1%FS±1℃
Supply voltage 220Vac,110Vac 50/60 Hz; 12Vac/dc, 24Vac/dc
Input type Thermocouple: K, J, R, S, B, E, N, T
RTD: Pt100, Cu50
Voltage: 0-5V, 1-5V
Current: 0-20mA, 4-20mA (need connect a 250ohm resistance between thermocouple input terminals, if the resistance is built-in, will can't change it to thermocouple inputs)

Note: 4-20mA input, 4-20mA output, the output has two types
Transmit output (Just XMTD2 has): The output is relative to the input, if the display is 0-100 degree, eg:
Input 4mA, Display 0, output 4mA
Input 12mA, Display 50, Output 12mA
Input 20mA, Display 100, Output 20mA
PID output: The output value is relative to the main output set value, if the display is 0-100 degree, eg:
Input 4mA, Display 0, output relative to the main output set value
Input 12mA, Display 50, Output relative to the main output set value
Input 20mA, Display 100, Output relative to the main output set value
Output type Electromagnetic relay, SSR, current, voltage, triac (not in one product, need to select)
Power consumption Less than 5 VA
Control method PID, or ON/OFF
Setting method Touch switch
Indication method 8-segment 4-digital display and LED indication
Alarms 1. Alarm quantity: XMTG: 1pcs, others: default is 1pcs, if 2pcs, need to be customized
2. Alarm form: N: No alarm
A: Deviation high
B: Deviation low
C: Deviation high/low
D: Band
E: Deviation high with hold action
F: Deviation low with hold action
G: Deviation high/low with hold action
H: Process high
J: Process low
K: Process high with hold action
L: Process low with hold action
P: Heater break (CTL-6), only AML1, when current output, don't have
S: Heater break (CTL-12), only AML1, when current output, don't have
R: Control loop break, either ALM1 or ALM2

XMTD2 alarm type:
00 no alarm
01 Measured value upper alarm
02 Measured value lower alarm
03 Deviation high
04 Deviation low
05 Deviation high/low
06 Band
When the decade is 1, it is standby alarm state
Operating temperature 0 to 50 ℃ (32 to 122 ℉)
Operating humidity 85% RH max, non-condensing
Alias name XMT series pid temperature controller, intelligent temperature controller
Output type and description
Electromagnetic relay Contact rating: 3A@250Vac, can make to 30A for XMTD, XMTA, XMT
Solid state relay Contact rating can be selected, order separately (Single phase 40AThree phase 40A)
Current 4-20mA
Voltage 0-5V
Triac Zero crossing pulse (default); phase shift pluse (just XMTD2 has)
Input type and measuring range
K 0-1372 ℃ (BoltPress springRingM12 probeM8 probeFlexible probeArmor high temperature resistantCustomized thread probe)
J Ring
R -50-1769 ℃
S 0-1769 ℃ (ProbeArmor)
B -50-1769 ℃
E 0-1000 ℃ (BoltPress springRingProbeCustomized thread probe)
N 0-1300 ℃
T -200-400 ℃
Pt100 -199.9-649.0 ℃ (BoltPress springRingProbePolish rodPolish rod waterproofPolish rod waterproof anticorrosiveFlexible probeCustomized thread probe)
Cu50 -50.0-150.0 ℃ (ProbePolish rod waterproof)
Voltage 0-5V, 1-5V 0.0-100.0 ℃
Current 0-20mA, 4-20mA 0.0-100.0 ℃