Products >> Relays >> Solid state relays >> ASH single phase C-AC
<

ASH-LA series single phase current to AC solid state voltage regulator

Model number and parameters
Model numberLoad currentLoad voltageOnline store: 
ASH-10LA10A24-380VacUS $6.74/ pieceOrder
ASH-25LA25A24-380VacUS $7.14/ pieceOrder
ASH-40LA40A24-380VacUS $7.66/ pieceOrder
ASH-60LA60A24-380Vac
ASH-80LA80A24-380Vac
ASH-100LA100A24-380Vac
Suitable maximum load power
Load current (A) 10 25 40 60 80 100
220V resistive load power (KW) 1.1 2.8 4.4 6.6 8.8 11
220V inductive load power (KW) 0.4 0.8 1.3 1.9 2.6 3.2
General
Model number ASH-LA series
Rated input control current 4-20mA
Control type Phase control
On-state leakage current 2mA max
On-state voltage drop at Imax 1.5Vac
Matched heat sink ≤40A: FHSI01-50, ≤60A: FHSI02-50, ≤120A: FHSI03-100
Matched thermal grease HZ-KS101
Dielectric strength 2500VAC 50/60Hz for 1 minute
Insulation resistance 1000 MΩ min at 500 VDC
External dimensions 57.4x44.8x28mm
Terminals Screw
Operational temperature -30 to 75℃
Operational humidity 95% max no condensation
Alias name ASH-LA series single phase voltage adjustable SSR
Advantage
1. Features:
Solid state relay is a non-contact on-off electronic switch, is four-terminal active device, two terminals are input control terminal, the other ends are output control terminal, it has optical isolation in the middle of them. Add DC or pulse signal to the input terminal, the output terminal's state can be changed from off to on (If it is no signal, it is off state), so as to control bigger load.
2. Typical applications:
This product can be widely used in electric heating thermostat equipment, remote control systems, industrial automation and control equipment, lights, stage lighting control equipment, instrument, medical equipment, etc. It has more superiority in some occasion of requiring shock-proof, corrosion-resistant, moisture-proof, explosion-proof.
3. Parameter Description:
1). Inrush current (grid one week) 700% output on-state voltage drop 1.5V.
2). Static voltage rise rate dvs/dt 100v/us operation temperature range -40 to 80 ℃.
3). Commutation voltage rise rate dvs/dt 100v/us zero-crossing SSR start delay 10ms maximum.
4). Leakage current (no RC absorbing circuit) is less than 1mA, SSR shut delay 10ms maximum.
5). Zero-crossing SSR zero-area 15V power frequency 50/60HZ.
Note 1. Model selection method: calculate the load current, according to load type, multiply the balance factor.
Resistive load: balance factor is 2 times, such as incandescent lamp, resistance wire, oven, heating rod.
Inductive load: balance factor is 7 times, such as: transformer, coil, fan motor, pump motor.
Example: 220V 3KW resistive load. 3KW/220V*2=27.3, select 40A specification.

2. To use product long and safely, please install the product with corresponding heat sink and fan.
ASH-LA series single phase current to AC solid state voltage regulator drawing
ASH-LA series single phase current to AC solid state voltage regulator structure figure