Model number and parameters
Model number NC1-09 NC1-12 NC1-18 NC1-25 NC1-32 NC1-40 NC1-50 NC1-65 NC1-80 NC1-95
Online store:  US $7.03 - 15.69/ pieceOrder (8) US $9.48 - 16.59/ pieceOrder (8) US $9.89 - 18.83/ pieceOrder (8) US $10.63 - 24.67/ pieceOrder (8) US $16.65 - 29.84/ pieceOrder (8) US $26.23 - 48.81/ pieceOrder (4) US $29.21 - 54.65/ pieceOrder (4) US $39.3 - 60.26/ pieceOrder (4) US $52.66 - 64.53/ pieceOrder (4) US $54.11 - 69.02/ pieceOrder (4)
Rated operational Current (AC-3) (A) at 380V 9 12 18 25 32 40 50 65 80 95
Rated operational Current (AC-3) (A) at 660V 6.6 8.9 12 18 21 34 39 42 49 49
Rated thermal current (A) 20 20 32 40 50 60 80 80 95 95
Maximum power (KW) at 220V 2.2 3 4 5.5 7.5 11 15 18.5 22 25
Maximum power (KW) at 380V 4 5.5 7.5 11 15 18.5 22 30 37 45
Maximum power (KW) at 660V 5.5 7.5 10 15 18.5 30 37 37 45 45
Mechanical life 104(ops) 1000 1000 1000 1000 800 800 800 800 600 600
AC3 electrical life 104(ops) 100 100 100 100 80 80 60 60 60 60
Maximum AC3 operations for 1 hour 1200 1200 1200 1200 600 600 600 600 600 600
AC4 electrical life 104(ops) 20 20 20 20 20 15 15 15 10 10
Maximum AC4 operations for 1 hour 300 300 300 300 300 300 300 300 300 300
Pick up (VA) 70 70 70 110 110 220 220 220 220 220
Sealed (VA) 9 9 9.5 14 14 57 57 57 57 57
Matched fuse NT00-20 NT00-20 NT00-32 NT00-40 NT00-50 NT00-63 NT00-80 NT00-80 NT00-100 NT00-125
Cabling capacity-1 flexible wire size (mm2) 2.5 2.5 4 4 6 10 16 25 50 50
Cabling capacity-1 solid or stranded wire size (mm2) 4 4 6 6 10 16 25 25 50 50
Cabling capacity-2 flexible wire size (mm2) 2.5 2.5 4 4 6 10 16 25 25 25
Cabling capacity-2 solid or stranded wire size (mm2) 4 4 6 6 10 - - - - -
General
Model number NC1 series
Rated coil voltage 24, 36, 48, 110, 220, 380VAC; 24VDC
Pick up voltage 0.85 to 1.10Us
Drop out voltage 0.2 to 0.75Us
Rated operational voltage 380V/660V
Rated Insulating voltage 660V
Number of poles <40A: 3P+NO / 3P+NC; ≥40A: 3P+NO+NC
Operating frequency limits 50/60Hz
Auxiliary contacts rated thermal current 10A
Auxiliary contact electrical life (AC-15,360VA) (OPS) 1x104
Auxiliary contact electrical life (DC-13,33W) (OPS) 1x104
Auxiliary contact min. available load 6V 10mA
Operating altitude 2000m max
Operating position (relative to normal mounting position) ±5 degree
Pollution degree 3
Matched auxiliary contact NC1 series DC contactor auxiliary contact
Operating temperature -5 to +40 ℃